Dielectric strength

All insulating materials fail at some level of applied voltage, and ‘dielectric strength’ is the voltage  a  material  can  withstand  before breakdown  occurs.  Dielectric  strength  is  measured through the thickness of the material (taking care to avoid surface effects) and is normally expressed  as  a  voltage  gradient  (volts  per  unit  length).  Note  that  the  voltage  gradient  at breakdown is much higher for very thin test pieces (<100µm thick) than for thicker sections.

The value of dielectric strength for a specimen is also influenced by its temperature and ambient humidity, by any voids or foreign materials in the specimen, and by the conditions of test, so that it is often difficult to compare data from different sources.

Test variables include electrode configuration and specimen geometry, and the frequency and rate of application of the test voltage. Standard strategies include:

•     The ‘short-time’ test, increasing the voltage from zero at a predetermined rate (usually between 100 and 3,000V/sec) until breakdown occurs

•     The ‘step-by-step’ test, initially applying half the short-time breakdown voltage, and then increasing this in equal increments, holding each level for a set period of time.